A. There is a code necessity for just a vapor retarder in certain kinds of assemblies, but there is no need for your vapor barrier. Your layer of rigid foam is now a vapor retarder. No further more vapor retarding layer should be set up.

If this have been my residence, and When the fiberglass batts are noticeable, I'd personally pull the entire insulation out of some rafter bays to view what is up there.

I ordered a disaster of a household that was partly remodeled, It really is in Zone sixteen (a California designation comparable to IRC zones). It has a 6/12 vaulted ceiling over the living/kitchen space. The roof is held up by two prolonged beams that run four toes out parallel towards the ridge , Consequently there is absolutely no straight air path a how up to the height ridge beam.

Ken's detail (#ten) does a fantastic career of cold local climate basic safety. It's got what we are seeking: Good airsealing at the interior, fluffy stuff in the middle, and excellent drying channels for h2o vapor at the best. By modifying from the very low permeability sheeting to a significant permeability membrane (at top rated) with venting above, there is no a lot more issue for roof rot though concurrently wind washing is prevented in the bays by the air & water limited membrane with taped edges and seams. It seems to me to generally be an extremely tough assembly.

"R-19 batts are extremely air permeable, and on extensive unobstructed rafter bays you may have really a stack influence. It won't take a large level of air leakage to offer some drying there. Also, In the event the batts are unfaced or kraft-confronted, the drying towards the interior can be significant.

My guidance could well be to seal the existing vents. If insulation contractors in your area are putting in three to four inches of closed-cell spray foam higher than the roof sheathing, it's not necessary to be concerned about condensation or humidity accumulation inside your sheathing.

You are not the one individual with this particular worry. For those who (such as you) are concerned about the issue, There are 2 possibilities:

Will it make sense to spray and Lower and cobble four inch closed cell foam/board on underside of sheathing followed by fiberglass In the bays and one inch of eps/iso under the rafter (to stop thermal have a peek here bridging) just before finishing with drywall? Will I make a vapor sandwich and far better go away the final EPS and acknowledge the thermal bridging?

You happen to be in local climate zone 5. I stated the least R-values for the approach you will be having in one of the paragraphs previously mentioned, through which I wrote, "According to .

With This technique , there's no issues with an entire peel-stick roof underlayment on top of the deck is there? I have a metal roof on this venture as well as the underlayment is going to be thoroughly adhered for the roof sheathing.

one. Your recommendation is just a slight variation with a detail which is presently talked about in my website, specifically cellulose put in that has a vent channel involving the very best of your cellulose and the roof sheathing.

Alright, so I am a bit apprehensive reading through this thread. I've an awesome space that may be paneled in addition to the rafters, which can be 4x8, And that i mounted sloped cans and was about to insulate and end ceilings. My Major reason of accomplishing this is that the roof is instantly about the beams and it gets very scorching in the summer, winter not a great deal of of trouble as I are in San Diego and temps not often dip underneath freezing.

Back again into the vent idea. I actually Believe venting a roof that is definitely airsealed in the inside well and constructed without vent chutes is perhaps the best way to Establish cathedral ceilings.

Builders address this problem by furring down or scabbing on more framing underneath the rafters to deepen the rafter bays.